2 items require attention within 30 days • 1 system approaching end of life
| Item | Condition | Age | Notes |
|---|---|---|---|
| Furnace Oil-fired, Kerr Comet |
Fair | 12 yrs | Running but noisy ignition. Filter replaced on-site. Last serviced Oct 2025. Recommend annual service before November. Expected lifespan: 18–22 years. 2 photos |
| Oil Tank Indoor, 910L steel |
Good | 8 yrs | No corrosion, legs stable, fuel line dry. 60% full. Vent whistle audible. 1 photo |
| Chimney & Flue | Fair | — | Mortar joints showing wear at cap level. Recommend chimney sweep and mortar repair this summer. 1 photo |
| Heat Distribution Baseboard hot water |
Good | — | Even heat all rooms. No cold spots. Baseboards clear of obstructions. |
| Item | Condition | Age | Notes |
|---|---|---|---|
| Water Heater Electric, 60 gal Bradford White ACTION REQUIRED |
Poor | 14 yrs | Rust visible at tank base. Anode rod never replaced. Pressure relief valve dripping. Expected lifespan: 10–15 years. Recommend replacement before October 2026. Est. $2,400–$3,200. 3 photos |
| Main Water Supply Copper |
Good | — | No corrosion, shutoff valve turns freely. Good pressure throughout. |
| Waste Lines | Good | — | All drains flowing well. No gurgling. Cleanout accessible. |
| Fixtures & Faucets | Good | — | Kitchen faucet slight drip — monitor. All shut-offs operational. |
| Item | Condition | Age | Notes |
|---|---|---|---|
| Main Panel Square D, 200A |
Good | 15 yrs | No double taps, breakers labeled, no burn marks. 4 spare slots. 1 photo |
| GFCI Outlets ACTION REQUIRED |
Poor | — | Kitchen GFCI failed test — would not trip. Bathroom GFCI passed. Replace kitchen GFCI immediately. Est. $150–$250. 1 photo |
| Smoke & CO Detectors | Good | 3 yrs | All 4 units tested and functional. Batteries replaced on-site. |
| Item | Condition | Age | Notes |
|---|---|---|---|
| Roof Covering Asphalt shingles, architectural |
Fair | 18 yrs | Granule loss on south-facing slope. No active leaks. 3–7 years remaining. Budget $8,000–$14,000 for replacement. 2 photos |
| Gutters & Downspouts | Good | — | Clean, properly sloped, discharging away from foundation. Extensions in place. |
| Soffit & Fascia | Good | — | No rot, vents clear, paint good. |
GFCI outlet replacement (kitchen)
Water heater replacement (60 gal electric)
Chimney mortar repair + sweep
Full roof replacement (asphalt shingles)